SINGLE OUTPUT (120W)
                     
    FEATURES:        SPECIFICATIONS:
  • Single phase input
  • Built in transient protector & EMI filter
  • Protection against short circuit , overload
    & overvoltage
  • Low ripple & noise
  • Cooling by free air convection
  • Power OK indication, terminations, output
    set control & rating details on front
  • 100% full load burn in test
  • Low cost
  • High reliability
  • Compact
  • DIN rail mountable.
  • AC input voltage range .......... 90 - 130VAC & 180 - 270VAC
  • AC input current(max) ........... 3A at 110VAC & 1.5A at 230VAC
  • AC inrush current ..................16A at 110VAC & 32A at 230VAC
  • Input frequency ..................... 47 ~ 63 Hz
  • Efficiency ............................. 70 ~75%
  • Isolation ............................... Input - Output : 3KVAC , 1minute
                                                 Input - Earth : 2KVAC , 1minute
                                                 Output - Earth : 0.5KVAC , 1minute
  • Overload protection ............... 105% ~ 130% of full load
  • Line & load regulation ............ Better than 0.5%
  • Hold up time ......................... >20ms
  • Operating ambient ................. 0°C ~ 50°C, 95% RH
  • Storage temperature ............. -20°C ~ 85°C
  • Weight ................................. 530 grams
  • Mounting .............................. 35mm DIN rail
Order Code
Output
Ripple & noise
Overvoltage
Protection
I/P: 230VAC
I/P: 110VAC
G31-120-12
G32-120-12
12V:8A
< 120mV
< 16V
G31-120-15
G32-120-15
15V:6A
< 150mV
< 20V
G31-120-24
G32-120-24
24V:5A
< 240mV
< 30V
G31-120-48
G32-120-48
48V:2.5A
< 350mV
< 63V
1. All parameters measured at 230VAC input, rated load and 25°C of ambient temperature unless otherwise specified .
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf &100uf parallel
    capacitor.
3. The power supply is intended to be installed as a component inside the enclosure of a final equipment. The final equipment must be
     re-confirmed that it still meets the EMC directives.
4. These units are designed for mounting on horizontal DIN rail. Ensure clearance of minimum 35mm from adjacent components for
     proper ventilation.
WE WELCOME DEVELOPMENT OF SMPS TO SUIT YOUR SPECIFIC REQUIREMENTS